The HARBAX automatic pressure switch comes in three versions for refrigeration and air conditioning: Low Pressure (HDPS1A), High Pressure (HDPS5A) and Dual Pressure (HDPS15A). The low model covers -0.2 to 7.5 bar, the high model covers 8 to 32 bar, and the dual model puts both a low-side range and a high-side cut-out scale in one housing. Every version has 1/4" brass flare connections, a scale you can read through the front window and automatic reset.
Low, High or Dual: Which HARBAX Pressure Switch Do You Need?
Low Pressure (HDPS1A)
Choose this model to watch the low side of a system. Its range runs from -0.2 to 7.5 bar (-3 to 109 psig), with a differential scale of 0.7 to 4 bar.
High Pressure (HDPS5A)
Choose this model to watch the high side. Its range runs from 8 to 32 bar (100 to 465 psig), with a differential scale of 2 to 6 bar.
Dual Pressure (HDPS15A)
Choose this model when one unit should watch both sides. The left window has the low-side range and differential scales, and the right window has the high-side CUT OUT scale from 8 to 32 bar. It has two 1/4" flare connections, one for each side.
Why Choose a HARBAX Automatic Pressure Switch?
- Three versions, one family: Pick low, high or dual control for compressors, condensers and other refrigeration equipment.
- Clear window scales: Range and differential are printed in both bar and psi (psig for range), so the setting can be read at a glance.
- Automatic reset: The switch resets by itself once pressure returns inside the set limits.
- 1/4" brass flare connection: Matches the common service-port flare fitting on HVAC and refrigeration lines.
- Separate range and differential adjustment: Each is set with its own screw, with a lock plate to hold the setting.
- Mounting hardware in the kit photos: A galvanised mounting bracket, a cover plate and screws in a bag are shown with the switches.
HARBAX Pressure Switch Specifications
| Specification | Low Pressure (HDPS1A) | High Pressure (HDPS5A) | Dual Pressure (HDPS15A) |
|---|---|---|---|
| Brand | HARBAX | HARBAX | HARBAX |
| Function | Automatic | Automatic | Automatic |
| Pressure sides | Low side only | High side only | Low side and high side in one housing |
| Adjustable range | -0.2 to 7.5 bar (-3 to 109 psig) | 8 to 32 bar (100 to 465 psig) | Low side: -0.2 to 7.5 bar (-3 to 109 psig) High side cut-out: 8 to 32 bar (100 to 465 psig) |
| Differential scale | 0.7 to 4 bar (10 to 55 psi) | 2 to 6 bar (35 to 85 psi) | Low side: 0.7 to 4 bar (10 to 55 psi) |
| Pressure connection | One 1/4" SAE flare, brass | One 1/4" SAE flare, brass | Two 1/4" flare, brass |
| Faceplate | SINGLE PRESSURE SWITCH, CE mark | SINGLE PRESSURE SWITCH, CE mark | DUAL PRESSURE SWITCH, CE mark |
| Mounting parts shown in kit photos | Bracket, cover plate, screws | Bracket, cover plate, screws | Bracket, cover plate, screws |
The readings above come from the scales printed on each switch.
| Manual data (HDPS1 and HDPS5) | Details |
|---|---|
| Switch type | SPDT changeover switch; terminals 1-2 open as pressure rises |
| Reset | Automatic reset |
| Maximum working pressure (PS/MWP) | HDPS1: 245 psig / 17 bar HDPS5: 510 psig / 35 bar |
| Connection thread | 7/16-20 UNF (1/4" SAE flare) |
| Temperature range | -40 to 65 °C |
| Load rating, AC 240 V | 8 A full load, 48 A locked rotor, 3 A pilot duty |
| Load rating, AC 120 V | 16 A full load, 96 A locked rotor, 3 A pilot duty |
| Load rating, DC 240 V | 12 W pilot duty |
| Rating basis | UL and CE regulations |
| Bellows and base | Phosphor copper bellows with brass base |
| Wiring | Copper wire only, terminal tightening torque 20 lb.in. |
The wiring, load, reset and temperature figures in the second table come from the HARBAX single pressure switch manual, which covers the HDPS1 and HDPS5 models. The dual model has its own faceplate scales, shown in the first table.
Adjusting Range and Differential
Set the range
The RANGE scale shows the main pressure setting. Turn the range screw to move the marker along the scale. On the dual model, the high side uses the CUT OUT scale in the right-hand window.
Set the differential
The DIFF scale shows the gap between the pressure where the switch operates and the pressure where it resets. It has its own adjusting screw.
Remove and refit the lock plate
Take off the lock plate before changing any setting, and fit it again afterwards so the setting stays put. After setting, confirm the switching points against your system's design pressures with a gauge.
Where to Use It: Applications
- High and low pressure control in refrigeration equipment
- Air conditioning and refrigeration systems
- Condensing unit and compressor protection
- Air pressure control in automation systems
- Replacement of an existing 1/4" flare pressure switch
Why Buy HARBAX Pressure Switches from Angstrom in Dubai?
- Dubai-based supplier of HVAC and refrigeration components, with delivery across the UAE.
- Low, high and dual models on one page, with the model numbers HDPS1A, HDPS5A and HDPS15A shown clearly.
- Full pressure ranges and connection details listed, so you can match the switch to your system before you order.
HARBAX Pressure Switch FAQ
What is the difference between a low, high and dual pressure switch?
A low pressure switch watches the low side of the system, a high pressure switch watches the high side, and a dual pressure switch combines both in one housing with two connections.
What pressure ranges do the HARBAX switches cover?
The low model covers -0.2 to 7.5 bar (-3 to 109 psig). The high model covers 8 to 32 bar (100 to 465 psig). The dual model has the low-side range plus a high-side cut-out scale of 8 to 32 bar.
Do these switches reset automatically?
Yes. They are automatic-reset switches, so they reset on their own when pressure returns to the set level.
What is the differential, and how do I set it?
The differential is the pressure gap between switching off and switching back on. The low switch offers 0.7 to 4 bar and the high switch offers 2 to 6 bar. Set it with the differential screw after removing the lock plate, then refit the plate.
What connection do they have?
The low and high models have one 1/4" SAE flare connection (7/16-20 UNF thread). The dual model has two 1/4" flare connections.
Which refrigerants and media can I use?
The standard models are made for Freon-type refrigerants, air and other non-corrosive media, with phosphor copper bellows and a brass base. Ammonia needs a stainless steel version, so these brass models are not for ammonia systems.
What temperature range and electrical rating apply?
The manual gives -40 to 65 °C and a rating of 8 A full load at AC 240 V and 16 A at AC 120 V for the single models. It also lists 3 A pilot duty on AC and 12 W on DC 240 V. Wire with copper only.
What maximum pressure can the single models take?
The manual lists 245 psig (17 bar) for HDPS1 and 510 psig (35 bar) for HDPS5.